Iai-america ACON-CG User Manual

Browse online or download User Manual for Hardware Iai-america ACON-CG. IAI America ACON-CG User Manual

  • Download
  • Add to my manuals
  • Print
  • Page
    / 196
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews

Summary of Contents

Page 1 - Positioner Type

Operation Manual Twelfth EditionACON-C/CGControllerPositioner Type

Page 2

5.1.1 External Input Specifications... 465.1.2 External Output Specifica

Page 3 - [Important]

867. Operation <Practical Steps> Warning: Excited phase detection is performed when the servo is turned on for the first time after the power

Page 4 - 1. Use Environment

877. Operation <Practical Steps>7.1.2 Position Table and Parameter Settings Required for Operation  Startup adjustment Immediately after the s

Page 5

887. Operation <Practical Steps> Full-scale operation This product provides energy-saving modes to reduce power consumption in situations where

Page 6

897. Operation <Practical Steps>7.2 Home Return Operation 7.2.1 Method Using the HOME Input Signal (PIO Pattern = 0 to 4) Since the home retur

Page 7

907. Operation <Practical Steps>Command position 1 to 256 input (PC1 ~ PC256) Start input (CSTR) Home return complete output (HEND) Completed po

Page 8 - CE Marking

917. Operation <Practical Steps>7.2.2 Method Used When No HOME Input Signal Is Available (PIO Pattern = 5) Since no home return signal (HOME) i

Page 9 - Table of Contents

927. Operation <Practical Steps>7.3 Positioning Mode (Back and Forth Movement between Two Points) Example of use in operation) The actuator mo

Page 10

937. Operation <Practical Steps>StartPosition complete MovingActuatorMovement is complete. Position table (Field(s) within thick line must be en

Page 11

947. Operation <Practical Steps>7.4 Push & Hold Mode Example of use in operation) The actuator is caused to move back and forth in the pus

Page 12

957. Operation <Practical Steps>Position table (Field(s) within thick line must be entered.) No.Position[mm]Speed[mm/s]Acceleration [G]Decelerat

Page 13

6.2.3 Speed Change during Movement ... 726.2.4 Operation at Different Accelerati

Page 14

967. Operation <Practical Steps>SpeedReturn actionReturned position250.34 mmTarget position280 mmPosition where the push & hold operation co

Page 15 - Safety Guide

977. Operation <Practical Steps>7.5 Speed Change during Movement Example of use in operation) The actuator speed is reduced at a certain point

Page 16 - Safety and Health

987. Operation <Practical Steps>Position table (Field(s) within thick line must be entered.) No.Position[mm]Speed[mm/s]Acceleration [G]Decelerat

Page 17

997. Operation <Practical Steps>7.6 Operation at Different Acceleration and Deceleration Settings Example of use in operation) Positioning is

Page 18 - Storage

1007. Operation <Practical Steps>1 msec or lessStartPosition complete MovingActuatorMovement is complete.Position table (Field(s) within thick l

Page 19

1017. Operation <Practical Steps>7.7 Pause Example of use in operation) Pause the actuator during movement. [Effective in PIO pattern = 0 to 4]

Page 20

1027. Operation <Practical Steps>Command position StartPosition complete Completed position PauseMovingActuator movement T1: 6 msec or more; ti

Page 21

1037. Operation <Practical Steps>7.8 Zone Signal Output Two types of zone output signals are available: zone output (ZONE1) and position zone o

Page 22

1047. Operation <Practical Steps>Controller [5] [2] [1][9][8] [3] [7] [6] [10] [4] PIOSignal nameStartCommand position 1 Command position 32 Com

Page 23 - 1. Overview

1057. Operation <Practical Steps>T1: 6 msec or more; time after selecting/entering a command position until the start input turns ON (The sca

Page 24

z Zone boundary... 125z Home return dire

Page 25 - 1.3 System Configuration

1067. Operation <Practical Steps>7.9 Incremental Moves Example of use in operation) Move the actuator from the home to the 30-mm position by is

Page 26

1077. Operation <Practical Steps>StartPosition complete MovingActuator1 msec or less Position table (Field(s) within thick line must be entered.

Page 27

1087. Operation <Practical Steps>7.9.1 Judgment Method of End Position Although completion judgment is based on the applicable count managed by

Page 28

1097. Operation <Practical Steps>7.9.2 Notes on Incremental Mode (1) Positioning mode If any incremental position number is selected and input

Page 29 - 1.5 Warranty

1107. Operation <Practical Steps>(2) Push & hold mode The following explains how the actuator will move if an incremental position number i

Page 30

1117. Operation <Practical Steps>z Push & hold operation using the incremental position number Example) If a position 2 command is input f

Page 31 - 2. Specifications

1127. Operation <Practical Steps>7.10 Jogging/Teaching Using PIO If the teaching type is selected, you can jog the actuator via operation from

Page 32 - 6SHFL¿FDWLRQV

1137. Operation <Practical Steps>Jogging/teaching timing T1: 20 msec or more; time after the current-position write input is turned ON until wr

Page 33

1147. Operation <Practical Steps>7.11 Operation of Solenoid Valve Mode 1 (7-point Type) Separate movement command inputs are provided for the t

Page 34 - 2.3 External Dimensions

1157. Operation <Practical Steps>Caution: Movement commands are executed based on the rise edge, so input each signal continuously for 6 msec o

Page 35 - 3.2 Supplied Voltage

9.5 Detail Connection Diagram... 14510. Troubleshoo

Page 36

1167. Operation <Practical Steps>z The movement command input operates in two modes. You can select the operation condition of the movement com

Page 37

1177. Operation <Practical Steps>z Handling of the pause (*STP) signal This signal is a contact B signal, meaning that it must remain ON while

Page 38 - 4. Wiring

1187. Operation <Practical Steps>7.12 Operation of Solenoid Valve Mode 2 (3-point Type) After the power has been turned on, input the rear end

Page 39 - (1) Wiring the power supply

1197. Operation <Practical Steps>z Meaning of position detected output signals (LS0, LS1, LS2) These signals are handled in the same manner as

Page 40

1207. Operation <Practical Steps>z Speed change during movement If the load is made of soft material or is a bottle or otherwise topples easily

Page 41

1217. Operation <Practical Steps>Occurrence of emergency situationFront end move command input (ST1) Rear end move command input (ST0) Rear end

Page 42

1228. Parameters8. Parameters 8.1 Parameter Table Category: a: Parameter relating to the actuator stroke range b: Parameter relating to the actuato

Page 43

1238. ParametersNo. Category Symbol Name Unit Default factory setting41 c FPIOOperating-mode input disable selection[0: Enable / 1: Disable]- 0 [Enabl

Page 44

1248. ParametersError detection rangeSoftware limit marginSoftware limitStrokeSoftware limitSoftware limit marginError detection range8.2 Detail Expl

Page 45

1258. Parametersz Zone boundary (1: No. 1/2 ZONM/ZONL 2: No. 23/24 ZNM2/ZNL2) These parameters set the range where the zone output signal (ZONE1) is

Page 47

1268. Parameters8.2.2 Parameters Relating to the Actuator Operating Characteristics z PIO jog speed (No. 26 IOJV) When the selected PIO pattern is “

Page 48

1278. Parametersz Current-limiting value during home return (No. 13 ODPW)The factory setting conforms to the standard specification of the actuator.z

Page 49 - Input power supply

1288. ParametersMove command Servo status Actuator movement Servo on Automatic servo-off mode (A green LED blinks.) Target positionT: Delay time (se

Page 50

1298. Parametersz Push speed (No. 34 PSHV) This parameter defines the push speed to be applied after the actuator reaches the target position in push

Page 51

1308. Parametersz Enable function (No. 42 FPIO) Whether to enable or disable the deadman switch function on an ANSI-type teaching pendant is defined

Page 52

1318. Parametersz Home-sensor input polarity (No. 18 AIOF) Parameter No. 18 defines the input polarity of the home sensor. With the current models

Page 53

1328. Parametersz Ball screw lead length (No. 77 LEAD) This parameter defines the ball screw lead length. A default value appropriate for the chara

Page 54

1338. ParametersIf the actuator is moved in the order to positions 1 Æ 2 Æ 3 Æ 4, the actuator will operate differently depending on whether or not sh

Page 55

1348. Parameters8.2.3 Parameters Relating to the External Interface z PIO pattern selection (No. 25 IOPN) Select the PIO operation pattern in parame

Page 56

1358. Parametersz Movement command type (No. 27 FPIO) Parameter No. 27 defines the operation conditions via the movement command inputs (ST0 to ST6)

Page 57 - Encoder control signal

1Safety Guide When designing and manufacturing a robot system, ensure safety by following the safety precautions provided below and taking the necessa

Page 58

1368. Parametersz Pause input disable selection (No. 15 FPIO) Parameter No. 15 defines whether the pause input signal is disabled or enabled. Setting

Page 59 - CB-RCA-SIO***

1378. Parametersz Output mode of position complete signal (No. 39 FPIO) This parameter is effective when any PIO pattern other than “5” [Solenoid val

Page 60 - 5.1 Interface Circuit

1388. Parametersz Silent interval multiplier (No. 45 SIVM) This parameter is not used for this controller. It is applied to controllers of RS485 seri

Page 61

1398. Parameters8.2.4 Servo Gain Adjustment Before the shipment, the servo has been adjusted in accordance with the standard specification of the actu

Page 62

1408. Parametersz Speed loop integral gain (No. 32 VLPT) Parameter No. Unit Input range Default 32 --- 1 ~ 217270Set individually in accordance with

Page 63

1413&7HDFKLQJ3HQGDQW&RQQHFWLRQ0HWKRGLQ0XOWLD[LV&RQ¿JXUDWLRQV9. PC/Teaching Pendant Connection Method in Multi-axis Configurati

Page 64

1423&7HDFKLQJ3HQGDQW&RQQHFWLRQ0HWKRGLQ0XOWLD[LV&RQ¿JXUDWLRQV9.2 Name and Function of Each Part of the SIO Converter This is a

Page 65

1433&7HDFKLQJ3HQGDQW&RQQHFWLRQ0HWKRGLQ0XOWLD[LV&RQ¿JXUDWLRQV[2] Link-connection terminal block (TB1) A connection port for lin

Page 66

1443&7HDFKLQJ3HQGDQW&RQQHFWLRQ0HWKRGLQ0XOWLD[LV&RQ¿JXUDWLRQV9.3 Address Switch Set an address (0 to 15) as a hexadecimal (0 to

Page 67

1453&7HDFKLQJ3HQGDQW&RQQHFWLRQ0HWKRGLQ0XOWLD[LV&RQ¿JXUDWLRQV9.5 Detail Connection Diagram (*1) The user must provide the two-

Page 68

2Requirements for Industrial Robots under Ordinance on Industrial Safety and Health Work area Work condition Cutoff of drive source Measure ArticleSi

Page 69 - CSTR/PWRT

1463&7HDFKLQJ3HQGDQW&RQQHFWLRQ0HWKRGLQ0XOWLD[LV&RQ¿JXUDWLRQVWhen connecting a PC to ACON without using an SIO converter (ground

Page 70 -  Start (CSTR)

14710. Troubleshooting10. Troubleshooting 10.1 Action to Be Taken upon Occurrence of Problem Upon occurrence of a problem, take an appropriate action

Page 71 -  Servo ON (SON)

14810. Troubleshooting10.2 Alarm Level Classification Alarms are classified into two levels based on the corresponding symptoms. Alarm level ALM lam

Page 72 -  Operation mode (MODE)

14910. Troubleshooting10.3 Alarm Description Output Using PIO In PIO patterns 0 to 3 (64 to 512-point positioning type), alarm information can be out

Page 73 -  Jog (JOG+, JOG-)

15010. Troubleshooting10.4 Alarm Description and Cause/Action (1) Message level alarms Code Error name Cause/Action 092 PWRT signal detected during

Page 74

15110. Troubleshooting151noitcA/esuaCemanrorrEedoC0BA Home sensor notdetectedThis error indicates that the actuator equipped with the home check senso

Page 75 -  Position complete (PEND)

15210. TroubleshootingCode Error name Cause/Action 0D9 Software stroke limit overtravel error Cause: [1] The actuator installed vertically overshot

Page 76 -  Write completion (WEND)

15310. Troubleshooting(2) Cold-start level alarms Code Error name Cause/Action 0A1 Parameter data error Cause: The input range of parameter range

Page 77 -  Alarm (*ALM)

15410. TroubleshootingCode Error name Cause/Action 0CA Overheating Cause: [1] This error indicates that the temperature around the power transisto

Page 78 -  Emergency stop (*EMGS)

15510. TroubleshootingCode Error name Cause/Action 0F4 Unmatched PCB This controller uses a different motor drive circuit depending on the motor ca

Page 79 - 6. Data Entry <Basics>

3Applicable Models of IAI’s Industrial RobotsMachines meeting the following conditions are not classified as industrial robots according to Notice ofM

Page 80

15610. Troubleshooting10.5 Messages Displayed during Operation Using the Teaching Pendant This section explains the warning messages that may be disp

Page 81

15710. TroubleshootingCode Message name Description 180 Address change OK 181 Controller initialization OK 182 Home change all clear 183 I/O func

Page 82

15810. TroubleshootingCode Message name Description 30C No connected axis This message indicates that no controller address is recognized. Cause:

Page 83

15910. Troubleshooting10.6 Specific Problems z I/O signals cannot be exchanged with the PLC. Cause: [1] The 24-V I/O power supply is connected in re

Page 84 - 6.2.1 Positioning Mode

16010. Troubleshootingz Home return ends in the middle in a vertical application.Cause: [1] The ball screw is receiving torsional stress due to the af

Page 85

161* Appendix* Appendix List of Specifications of Connectable Actuators The specifications included in this specification list are limited to those ne

Page 86

162* AppendixMotor outputLeadMinimumspeedMaximum speedMaximum acceleration/ decelerationMinimum push force Maximum pushforceRated push speedActuatorse

Page 87 - “Zone boundary+”

163* AppendixMotor outputLeadMinimumspeedMaximum speedMaximum acceleration/ decelerationMinimum push force Maximum pushforceRated push speedActuatorse

Page 88 - 6.2.7 Home Return

164* AppendixMotor outputLeadMinimumspeedMaximum speedMaximum acceleration/ decelerationMinimum push force Maximum pushforceRated push speedActuatorse

Page 89

165* AppendixMotor outputLeadMinimumspeedMaximum speedMaximum acceleration/ decelerationMinimum push force Maximum pushforceRated push speedActuatorse

Page 90

4Notes on Safety of Our Products Common items you should note when performing each task on any IAI robot are explained below. No. Task Note1 Model se

Page 91

166* AppendixMotor outputLeadMinimumspeedMaximum speedMaximum acceleration/ decelerationMinimum push force Maximum pushforceRated push speedActuatorse

Page 92

167* AppendixMotor outputLeadMinimumspeedMaximum speedMaximum acceleration/ decelerationMinimum push force Maximum pushforceRated push speedActuatorse

Page 93

168* AppendixMotor outputLeadMinimumspeedMaximum speedMaximum acceleration/ decelerationMinimum push force Maximum pushforceRated push speedActuatorse

Page 94

169* AppendixMotor outputLeadMinimumspeedMaximum speedMaximum acceleration/ decelerationMinimum push force Maximum pushforceRated push speedActuatorse

Page 95

170* AppendixMotor outputLeadMinimumspeedMaximum speedMaximum acceleration/ decelerationMinimum push force Maximum pushforceRated push speedActuatorse

Page 96 - 7.1 How to Start

171* AppendixMotor outputLeadMinimumspeedMaximum speedMaximum acceleration/ decelerationMinimum push force Maximum pushforceRated push speedActuatorse

Page 97

172* AppendixMotor outputLeadMinimumspeedMaximum speedMaximum acceleration/ decelerationMinimum push force Maximum pushforceRated push speedActuatorse

Page 98

173* AppendixMotor outputLeadMinimumspeedMaximum speedMaximum acceleration/ decelerationMinimum push force Maximum pushforceRated push speedActuatorse

Page 99

174* AppendixAppendixPositioning Sequence Given below is an example of basic sequence for creating a positioning sequence indicates PIO signal

Page 100

175* AppendixAppendixPENDMNNOSSJMNM(A)PPOOQQQPPBJOSRORRCurrent positioning completed position (Positioning circuit for position 2) Positioning start r

Page 101 -  Startup adjustment

5No. Task Note(1) Installing the robot, controller, etc. z Be sure to firmly secure and affix the product (including its work part). If the product t

Page 102 -  Full-scale operation

176* AppendixAppendixSPC1PC2PC4PC8Timer 2CSTRTimer 2 JOPosition 3 set signalPosition 5 set signalCommand position 1Command position 2Position 6 set si

Page 103 - 7.2 Home Return Operation

177* AppendixAppendixRecording of Parameters Recorded date: Category: a: Parameter relating to the actuator stroke range b: Parameter relating to t

Page 104

178* AppendixAppendixNo. Category Name Unit Recorded data 41 c Operating-mode input disable selection [0: Enable / 1: Disable] -42 b Enable functio

Page 105

179Change HistoryAppendixRevision Date Description of Revision2007.032007.042009.012009.082009.122010.022010.052010.092011.01First editionSecond editi

Page 108 - 7.4 Push & Hold Mode

Manual No.: ME0176-12A (December 2012)The information contained in this document is subject to change without notice for purposes ofproduct improvemen

Page 110

6No. Task Note4 Installation/ startup z Implement safety measures so that the product cannot be started only by turning on the power. If the product

Page 111

7No. Task Note7 Automatic operationz Before commencing automatic operation, make sure no one is inside the safety fences. z Before commencing automat

Page 112

8Indication of Cautionary Information The operation manual for each model denotes safety precautions under “Danger,” “Warning,” “Caution” and “Note,”

Page 113

91. Overview1. Overview 1.1 Introduction This product is a dedicated RCA, RCA2 and RCL actuator controller that provides the same functions of the RCS

Page 114

101. Overview1.2 How to Read the Model Number<Series><Type>C: Positioner type (internal drive-power cutoff relay)CG: Safety category type

Page 115 - 7.7 Pause

111. OverviewStandard teaching pendant<CON-TRCM-T> External EMG switch Host system <PLC>Supplied flat cableInput power supply 24 VDC 24-

Page 116 - 6 msec or more

121. OverviewHost system <PLC> Standard teaching pendant<CON-TRCM-T> Supplied flat cableInput power supply 24 VDC24-VDC I/O power supplyP

Page 117 - 7.8 Zone Signal Output

131. Overview1.4 Procedure from Unpacking to Test Operation and Adjustment If you are using this product for the first time, carry out each step by r

Page 118

141. Overview6.Turn on the servo Confirm that the slider or rod is not contacting a mechanical end. If the slider/rod is contacting a mechanical end,

Page 119

151. Overview1.5 Warranty1.5.1 Warranty PeriodOne of the following periods, whichever is shorter:18 months after shipment from our factory12 months af

Page 120

Please Read Before Use Thank you for purchasing our product. This Operation Manual explains the handling methods, structure and maintenance of this pr

Page 121

161. Overview1.5.5 Conditions of Conformance with Applicable Standards/Regulations, Etc., and Applications[1] Medical equipment pertaining to mainten

Page 122 - 190.5 mm

176SHFL¿FDWLRQV2. Specifications 2.1 Basic Specifications Specification item Positioner type (with internal drive-power cutoff relay) Safety catego

Page 123

186SHFL¿FDWLRQV2.2 Name and Function of Each Part of the Controller  Indication of PIO pattern number If you have multiple systems and a differe

Page 124 - 20 mm/s

196SHFL¿FDWLRQV Explanation of each switch [1] Address switch If multiple axes are used, the PC/teaching pendant must be plugged into/out of diff

Page 125

206SHFL¿FDWLRQV2.3 External Dimensions An external view and dimensions of the product are shown below. (Note) Refer to the operation manual for ea

Page 126 - Manual operation switching

213. Installation and Noise Elimination3. Installation and Noise EliminationPay due attention to the installation environment of the controller.3.1 In

Page 127

223. Installation and Noise Elimination3.3 Noise Elimination Measures and GroundingThe following explains the noise elimination measures that should b

Page 128

233. Installation and Noise EliminationFan50 mm or more50 mm or moreAirflow95 mm or more [2] DC solenoid valves, magnet switches and relays Measure:

Page 129

244. WiringRed White BlackController Connected to teaching pendant or PC External EMG switch Input power supply 24 VDC I/O flat cable Terminal block A

Page 130

254. Wiring4.1.2 Wiring the Power Supply/Emergency-Stop Switch (1) Wiring the power supply To connect multiple controllers, provide a relay terminal

Page 131

CAUTION1. Use EnvironmentACON controllers can be used in an environment of pollution degree 2 or equivalent.2. PC Software and Teaching Pendant Model

Page 132 - Execution of

264. Wiring(2) Wiring the emergency-stop switch In many cases multiple controllers are used in a single system. To provide an emergency-stop function

Page 133

274. WiringRepresentative connection examples are explained below. z Connecting the teaching pendant directly to the controller [1] Connecting multi

Page 134

284. Wiring[Controller 1] [Controller 2] [Controller 3] [Controller 4] EMG signal Teaching pendantRelayTeaching pendant Teaching pendant Teaching pend

Page 135 - Occurrence of

294. Wiring[2] Using a power supply other than the input power supply (Note) Use an auxiliary relay with a coil current of 0.1 A or less and connect

Page 136 - 8. Parameters

304. Wiring[3] Connecting the teaching pendant to a SIO converter Configure the contact circuit for the EMG switch on the teaching pendant using EMG1

Page 137

314. Wiring

Page 138

324. WiringController 0 V (NPN specification) 24 V (PNP specification) 24 V (NPN specification) 0 V (PNP specification) 24-VDC power for input/output

Page 139

334. Wiring4.2.2 Wiring the Power Supply/Emergency-Stop Switch (1) Wiring the power supply To connect multiple controllers, provide a relay terminal

Page 140

344. WiringEMG switchTeaching pendant Motor power supply External EMG reset switch External EMG circuit Controller power supply Coil current: 0.1 A or

Page 141

354. Wiring[Connection example of a multiple-axis configuration] Input power supply [Controller 1] [Controller 2] [Controller 3] Connect to 24-V ter

Page 142

CAUTION4. Initial Parameter Settings at StartupAfter applying power, at least the three parameters specified below must be set in accordance withthe s

Page 143

364. Wiring4.3 Connecting the I/O Cables z PIO pattern 0 [Positioning mode (Standard Type)] 0 [V] 0 [V] +24 [V] +24 [V] PIOController end (signal ab

Page 144

374. Wiringz PIO pattern 1 [Teaching mode (Teaching Type)] 0 [V] 0 [V] +24 [V] +24 [V] PIOBrown 1 Red 1 Orange 1 Yellow 1 Green 1 Blue 1 Purple 1 Gra

Page 145

384. Wiringz PIO pattern 2 [256-point mode (256-point type)] 0 [V] 0 [V] +24 [V] +24 [V] Controller end PIO (signal abbreviation) Output side Command

Page 146

394. Wiringz PIO pattern 3 [512-point mode (512-point type)] PIOOutput side Command position 1 Command position 2 Command position 4 Command position

Page 147

404. Wiringz PIO pattern 4 [Solenoid valve mode 1 (7-point Type)] PIODirect position command 0 Direct position command 1 Direct position command 2 Di

Page 148

414. Wiringz PIO pattern 5 [Solenoid valve mode 2 (3-point Type)] PIOOutput side Rear end move Front end move Intermediate point move Brake release O

Page 149

424. WiringCaution: When performing a continuity check of the flat cable, pay due attention not to expand the female pins in the connector. It may ca

Page 150

434. Wiring4.4 Connecting the Actuator 4.4.1 Wiring the ACON-C/CG and Actuator Use dedicated extension cables to wire the controller and actuator.

Page 151

444. Wiring(3) RCA2 integrated motor/encoder cableModel number: CB-ACS-MPA( indicates the cable length L. Example: 080 = 8 m)Housing: DF1E-3S-2.

Page 152

454. Wiring4.5 Connecting the Communication Cable Connect the communication cable to the SIO connector. Brown Yellow Red Orange Blue Green Pin No. Br

Page 153 - 8.2.4 Servo Gain Adjustment

CAUTION[2] Enabling/disabling the servo ON input signal (SON) The servo ON input signal has been added to allow for servo ON/OFF control on the PLC s

Page 154

465. I/O Signal Control and Signal FunctionsController ControllerExternal power supply Each inputExternal power supply Each inputInternal circuitInter

Page 155 - 9.1 Connection Example

475. I/O Signal Control and Signal FunctionsController External power supplyInternal circuitEach outputLoadLoadController External power supply Intern

Page 156

485. I/O Signal Control and Signal Functions5.2 PIO Patterns and Signal Assignments This controller provides six PIO pattern types to meet the needs

Page 157 - [6] Monitor LEDs

495. I/O Signal Control and Signal Functions5.2.1 Explanation of Signal Names The following explains the signal names, and gives a function overview

Page 158 - 9.4 Connection Cables

505. I/O Signal Control and Signal Functionsz PIO pattern = 1 [Teaching mode (Teaching type)] Category Signal name Signal abbreviationFunction overvi

Page 159

515. I/O Signal Control and Signal Functionsz PIO pattern = 2 [256-point mode (256-point type)] Category Signal name Signal abbreviationFunction over

Page 160

525. I/O Signal Control and Signal Functionsz PIO pattern = 3 [512-point mode (512-point type)] Category Signal name Signal abbreviationFunction over

Page 161 - 10. Troubleshooting

535. I/O Signal Control and Signal Functionsz PIO pattern = 4 [Solenoid valve mode 1 (7-point type)] Category Signal name Signal abbreviationFunction

Page 162

545. I/O Signal Control and Signal Functionsz PIO pattern = 5 [Solenoid valve mode 2 (3-point type)] Category Signal name Signal abbreviationFunction

Page 163

555. I/O Signal Control and Signal Functions5.2.2 Signal Assignment Table for Respective PIO Patterns When creating a PLC sequence or wiring signals,

Page 164 - (1) Message level alarms

CAUTIONx Changes to Zone Function Applicable application versions: V0015 and later Among the zone signal settings, those that result in “Zone set

Page 165

565. I/O Signal Control and Signal Functions5.3 Details of I/O Signal Functions An input time constant is provided for the input signals of this cont

Page 166

575. I/O Signal Control and Signal Functions Command position number (PC1 to PC256) When a movement command is effected upon OFF o ON of the start s

Page 167 - (2) Cold-start level alarms

585. I/O Signal Control and Signal Functions Alarm reset (RES) This signal provides two functions. [1] Reset the alarm output signal (*ALM) that tu

Page 168

595. I/O Signal Control and Signal Functions Jog (JOG+, JOG-) This signal is valid when the teaching mode (teaching type) is selected. During jogging

Page 169

605. I/O Signal Control and Signal Functions Movement to each position (ST0 to ST2) [Solenoid valve mode 2 (3-point type)] Since the number of posit

Page 170

615. I/O Signal Control and Signal Functions5.3.2 Details of Each Output Signal  Operating mode status (RMDS) The internal operating mode of the co

Page 171

625. I/O Signal Control and Signal Functions Home return completion (HEND) This signal is OFF immediately after the power is input, and turns ON in

Page 172

635. I/O Signal Control and Signal Functions Movement complete at each position (PE0 to PE6) [Solenoid valve mode 1 (7-point type)] When PIO pattern

Page 173 - 10.6 Specific Problems

645. I/O Signal Control and Signal Functions Emergency stop (*EMGS) This signal remains ON while the controller is normal, and will turn OFF if the

Page 174

656. Data Entry <Basics>6. Data Entry <Basics> To move the actuator to a specified position, a target position must be entered in the “Po

Page 175 - * Appendix

CE MarkingIf a compliance with the CE Marking is required, please follow Overseas Standards Compliance Manual (ME0287) that is provided separately.

Page 176

666. Data Entry <Basics>(4) Acceleration/deceleration x Enter the acceleration/deceleration at which to move the actuator, in [G].Basically, th

Page 177

676. Data Entry <Basics>“Push & hold operation” This field defines the maximum push distance after reaching the target position in push &

Page 178

686. Data Entry <Basics>S-motionSpeed Time (9) Acceleration/deceleration mode• This field defines the acceleration/deceleration pattern charact

Page 179

696. Data Entry <Basics>Primary delay filter Speed Time The actuator operates along acceleration/deceleration curves that are more gradual than

Page 180

706. Data Entry <Basics>6.2 Explanation of Modes 6.2.1 Positioning Mode Push = 0The actuator moves to the target position set in the “Position”

Page 181

716. Data Entry <Basics>(2) Work part was not contacted (missed) If the actuator does not still contact the work part after having moved the di

Page 182

726. Data Entry <Basics>(4) Positioning band was entered with a wrong sign Take note that if a value with a wrong sign is set in the “Positioni

Page 183

736. Data Entry <Basics>ON ONOFF*STP Actuator operation Target position Zone output (ZONE1)Actuator operation+ directionHomeValue set in paramet

Page 184

746. Data Entry <Basics>6.2.7 Home Return After the power is turned on, home return must be performed to establish the home position. The method

Page 185

756. Data Entry <Basics>6.2.8 Overview of Teaching Mode (Teaching Type) Depending on your system, it may be desirable to be able to use a touch

Page 186

Table of ContentsSafety Guide... 11.

Page 187

766. Data Entry <Basics>6.2.9 Overview of Solenoid Valve Mode 1 (7-point Type) The number of positioning points is kept small, or specifically

Page 188 - Positioning Sequence

776. Data Entry <Basics>[2] In case of positioning mode (standard type) Command position 1 input (PC1) Command position 2 input (PC2) Command p

Page 189 - Appendix

786. Data Entry <Basics>6.2.10 Overview of Solenoid Valve Mode 2 (3-point Type) This type provides a control method adjusted to that of an air

Page 190

796. Data Entry <Basics>Item Air cylinder ACONPositioncheck upon power ON Determined by an external detection sensor, such as a reed switch. Im

Page 191 - Recording of Parameters

806. Data Entry <Basics>Movementcommand Servo status ActuatormovementServo on Automatic servo-off mode (A green LED blinks.) Target position T:

Page 192

816. Data Entry <Basics>Also note that when the PIO pattern is “0,” “1,” “2,” “3” or “4,” the servo will turn off and therefore the position com

Page 193 - Change History

827. Operation <Practical Steps>7. Operation <Practical Steps> 7.1 How to Start 7.1.1 Timings after Power On  Procedure after initial

Page 194

837. Operation <Practical Steps>[10] Perform home return. z Overview of operation on the teaching pendant x In case of CON-T, press the “ADJ”

Page 195

847. Operation <Practical Steps> Procedure of Normal Operation The operating procedure in normal condition is specified below: [1] Reset the

Page 196 - 12.12.000

857. Operation <Practical Steps>Home positionMechanical endPower on positionEmergency stop not actuated (motor drive power supplied)Safety circu

Related models: ACON-C